control unit Micrologic 2.0 A, basic protections LI, ammeter measurement
Mfr. Part No.:
33071
APT Stock No.:
SE-33071
Brand:
Schneider Electric
Back Order
Need more stock?
Contact us for Est. Lead TimeSubtotal (1 unit)**
GHS 12,352.28
(Exc. VAT)
GHS 15,057.43
(Inc. VAT)
Available For Order
* Delivery dates may change based on your quantity and address.
Shipping & Policy
Payment Methods:

Shipping Cost:
Contact the supplier about freight and estimated delivery time.
Secure payments:
Every payment you make on aptghana.com is protected by the platform.
Return policy
Enjoy peace of mind with our 7-day return policy for used items, provided they are returned in their original packaging.
Shipping & Policy
Payment Methods:

Shipping Cost:
Contact the supplier about freight and estimated delivery time.
Secure payments:
Every payment you make on aptghana.com is protected by the platform.
Return policy
Enjoy peace of mind with our 7-day return policy for used items, provided they are returned in their original packaging.
Specifications
Main | |
---|---|
Product or component type | Control unit |
Trip unit name | MicroLogic 2.0 A |
Trip unit technology | Electronic |
Range compatibility | MasterPact NT MasterPact NW Compact NS Masterpact MT |
Device application | Distribution |
Number of poles | 4P 3P |
Protected poles description | 4t 3t 3t + N/2 |
Trip unit protection functions | Basic protection |
Protection type | for overload protection (long time) for instantaneous short-circuit protection |
Trip unit rating | 630 A at 50 °C 800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C 2000 A at 50 °C 2500 A at 50 °C 3200 A at 50 °C 4000 A at 50 °C 5000 A at 50 °C 6300 A at 50 °C |
Network type | AC |
Network frequency | 50/60 Hz |
Circuit breaker mounting mode | Fixed Drawout |
Complementary | |
---|---|
Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
[Ir] long-time protection pick-up adjustment range | 0.4...1 x In |
Long-time protection delay adjustment type tr | Adjustable 9 settings |
[tr] long-time protection delay adjustment range | 0.7…16.6 s at 7.2 x Ir 0.7…24 s at 6 x Ir 12.5…600 s at 1.5 x Ir |
Thermal memory | 20 mn |
Instantaneous protection pick-up adjustment type Ii | Adjustable 9 settings |