Auxiliary contact, Acti9 A9N, OF/SD+OF, 2 C/O, 100mA to 6A, 24VAC to 415VAC, 24VDC to 130VDC, top and bottom connection
Mfr. Part No.:
A9N26909
APT Stock No.:
SE-A9N26909
Brand:
SCHNEIDER ELECTRIC
In Stock: available
Need additional quantities?
Contact us for estimated lead timeSubtotal (1 unit)**
GHS 254.25
(Exc. VAT)
GHS 309.93
(Inc. VAT)
Available For Order
* Delivery dates may change based on your quantity and address.
Shipping & Policy
Payment Methods:

Shipping Cost:
Contact the supplier about freight and estimated delivery time.
Secure payments:
Every payment you make on aptghana.com is protected by the platform.
Return policy
Enjoy peace of mind with our 7-day return policy for used items, provided they are returned in their original packaging.
Can report the signaling to an Open/Closed or an Opening for Default Devices status
Compatible with standard applications with current from 100mA up to 6A
Compatible with Acti9 C120/C60H-DC
To be fixed with clips directly on the left of the MCB
Shipping & Policy
Payment Methods:

Shipping Cost:
Contact the supplier about freight and estimated delivery time.
Secure payments:
Every payment you make on aptghana.com is protected by the platform.
Return policy
Enjoy peace of mind with our 7-day return policy for used items, provided they are returned in their original packaging.
Compatible products

MAINFUNCTIONS (6)
Specifications
| Main | |
|---|---|
| range of product | Acti9 | 
| Product or component type | Double OC or fault contact | 
| Device short name | OF and OF or OF and SD | 
| Signal contacts composition | 2 C/O | 
| [In] rated current | 0.1…6 A at 24...250 V, AC 50/60 Hz 0.1…6 A at 24...240 V, AC 50/60 Hz 0.1…3 A at 415 V, AC 50/60 Hz 0.1…6 A at 24 V, DC 0.1…2 A at 48 V, DC 0.1…1.5 A at 60 V, DC 0.1…1 A at 130 V, DC 50/60 Hz | 
| 9 mm pitches | 1 | 
| Standards | EN/IEC 60947-5-1 GB/T 14048.5 | 
| Product certifications | CE UKCA | 
| Quality labels | EAC CCC | 
| Complementary | |
|---|---|
| [Ui] rated insulation voltage | 500 V | 
| [Uimp] rated impulse withstand voltage | 4 kV | 
| Local signalling | Mechanical indicator | 
| Mounting mode | Clip-on | 
| Mounting location | Left side of circuit-breaker | 
| Mounting support | DIN rail | 