Soft start-ATS22- 62A-400..440V-30kW

Mfr. Part No.:

ATS22D62Q

APT Stock No.:

SE-ATS22D62Q

Brand:

SCHNEIDER ELECTRIC

Currently Unavailable – Back Order Required

Subtotal (1 unit)**

GHS 13,632.15

(Exc. VAT)

GHS 16,358.58

(Inc. VAT)

Available For Back Order

Out of stock? No worries! You can back order this product.
To request a back order:

  • Tap the Request Back Order button below
  • Fill out the form with your Name, Email, Phone, and Company

Our team will review your request and contact you with availability and lead time.

* Delivery dates may change based on your quantity and address.

Shipping & Policy

Payment Methods:

Momo Page imagemastercardvise

Shipping Cost:

Contact the supplier about freight and estimated delivery time.

Secure payments:

Every payment you make on aptghana.com is protected by the platform.

Return policy

Enjoy peace of mind with our 7-day return policy for used items, provided they are returned in their original packaging.

Provide smooth starting, avoiding mechanical stresses and extending their service life

Reduce hearing discomfort for operators on the workfloor

Slim form factor improves versatility

Less cost to stock spares

Overcome difficult or high-torque starts

Description

Compatible products

Specifications

Dimensions Drawings

Frame Size B
Dimensions



Mounting and Clearance

Precautions
Standards

The Altistart 22 soft starter is compliant with pollution Degree 2 as defined in NEMA ICS1-1 or IEC 60664-1.

For environment pollution degree 3, install the Altistart 22 soft starter inside a cabinet type 12 or IP54.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

ATS22 soft starters are open devices and must be mounted in a suitable enclosure.

Failure to follow these instructions will result in death or serious injury.

Air Circulation

Leave sufficient free space to help the air required for cooling purposes to circulate from the bottom to the top of the unit.


Overheating

To avoid the soft starter to overheat, respect the following recommendations:

  • Mount the Altistart 22 Soft Starter within ± 10° of vertical.

  • Do not locate the Altistart 22 Soft Starter near heat radiating elements.

  • Electrical current through the Altistart 22 Soft Starter will result in heat losses that must be dissipated into the ambient air immediately surrounding the soft starter. To help prevent a thermal fault, provide sufficient enclosure cooling and/or ventilation to limit the ambient temperature around the soft starter.

  • If several soft starters are installed in a control panel, arrange them in a row. Do not stack soft starters. Heat generated from the bottom soft starter can adversely affect the ambient temperature around the top soft starter.


,
Mounting
Connection Between the Fan and the Altistart 22 Soft Starter


1
Altistart 22 Soft Starter
2
Fan


,
Wall mounted or Floor-standing Enclosure with IP 23 Degree of protection
Introduction

To help proper air circulation in the soft starter, grilles and forced ventilation can be installed.

Ventilation Grilles


Forced Ventilation Unit



Connections and Schema

Power Terminal
Cage Style


1
Ground connection

Power connections, minimum and maximum wiring capabilities, tightening torque

IEC cable

UL cable

Power supply and output to motor

Size/gauge

min

4 mm (a)

10 AWG (a)

max

50 mm

1/0 AWG

Tightening torque

min

8 N.m

70 lb.in

max

8 N.m

70 lb.in

Strip length

15 mm

0.6 in.

Power connections, minimum required wiring section

IEC cable

mm² (Cu 70°C/158°F) (1)

UL cable

AWG (Cu 75°C/167°F) (1)

16

4


,
230 Vac control, logic Inputs (LI) 24 Vdc, 3-wire control
With Line Contactor, Freewheel or Controlled Stop



,
230 Vac control, logic Inputs (LI) 24 Vdc, 2-wire control,freewheel stop



,
Connection in the motor delta winding in series with each winding
Wiring

ATS22 soft starters connected to motors with the delta connections can be inserted in series in the motor windings.

The following wiring requieres particular attention. It is documented in the Altistart 22 Soft start - soft stop unit user manual. Please contact Schneider Electric commercial organisation for further informations.


Example

A 400 V - 110 kW motor with a line current of 195 A (nominal current for the delta connection). The current in each winding is equal to 195/1.5 or 130 A. The rating is determined by selecting the soft starter with a permanent nominal current (ICL) just above this current.


Performance Curves

Motor Thermal Protection - Cold Curves
Curves


A
Class 10
B
Class 20
C
Class 30

Trip time for a Standard Application (Class 10)

3.5 ln

32 s

Trip time for a Severe Application (Class 20)

3.5 ln

63 s

Trip time for a Severe Application (Class 30)

3.5 ln

95 s


,
Motor Thermal Protection - Warm Curves
Curves


A
Class 10
B
Class 20
C
Class 30

Trip time for a Standard Application (Class 10)

3.5 ln

16 s

Trip time for a Severe Application (Class 20)

3.5 ln

32 s

Trip time for a Severe Application (Class 30)

3.5 ln

48 s