Earth-leakage add-on protection module, ComPact NSX 250, MH type, 200 VAC to 440 VAC, 30 mA to 10 A, 4 poles
Mfr. Part No.:
LV431536
APT Stock No.:
SE-LV431536
Brand:
Schneider Electric
Back Order
Need more stock?
Contact us for Est. Lead TimeSubtotal (1 unit)**
GHS 10,044.35
(Exc. VAT)
GHS 12,244.06
(Inc. VAT)
Available For Order
* Delivery dates may change based on your quantity and address.
Shipping & Policy
Payment Methods:

Shipping Cost:
Contact the supplier about freight and estimated delivery time.
Secure payments:
Every payment you make on aptghana.com is protected by the platform.
Return policy
Enjoy peace of mind with our 7-day return policy for used items, provided they are returned in their original packaging.
Description
It is a MH Vigi add-on module for 4 poles Compact NSX 250 and EasyPact CVS 250. It provides an earth-leakage protection when installed directly on the device terminals. It directly actuates the trip unit in case of insulation fault. The addition of this Vigi add-on module does not modify Compact NSX 250 or EasyPact CVS 250 characteristics. It is a MH type module in 4 poles version, self-powered by the input voltage. The operational voltage for the Vigi add-on is from 200VAC to 440VAC 50/60Hz. The sensitivity is adjustable from 30mA to 10A, the time delay is also adjustable. The dimensions of the circuit breaker equipped with this module are 140mm x 236mm x 86mm.
Shipping & Policy
Payment Methods:

Shipping Cost:
Contact the supplier about freight and estimated delivery time.
Secure payments:
Every payment you make on aptghana.com is protected by the platform.
Return policy
Enjoy peace of mind with our 7-day return policy for used items, provided they are returned in their original packaging.
Specifications
Main | |
---|---|
Range of product | ComPact NSX100...250 |
Range | ComPact |
Product or component type | Vigi add-on |
Device application | Wiring |
Range compatibility | ComPact ComPact NSX250 circuit breaker EasyPact EasyPact CVS250 circuit breaker |
Poles description | 4P |
[In] rated current | 250 A |
Earth-leakage add-on module name | MH |
Earth-leakage protection class | Class A |
Residual earth-leakage sensitity adjustment type | Adjustable 5 settings |
Earth-leakage sensitivity | 0.03 A 0.3 A 1 A 3 A 10 A |
Residual earth-leakage time delay adjustment type | Adjustable 4 settings |
[Δt] residual earth-leakage time delay adjustment | 0 ms 310 ms 60 ms 150 ms |
Complementary | |
---|---|
Network type | AC |
Network frequency | 50/60 Hz |
[Ue] rated operational voltage | 200...440 V AC 50/60 Hz conforming to IEC 60947-2 |
Earth-leakage protection | With |
Maximum breaking time | 800 ms |
Overvoltage category | Class II |