Motor Voltage& PTC control relay-24-240VAC/DC-2NO

Mfr. Part No.:

RM35TM250MW

APT Stock No.:

SE-RM35TM250MW

Brand:

SCHNEIDER ELECTRIC

In Stock: available

Need additional quantities?

Contact us for estimated lead time

Subtotal (1 unit)**

GHS 1,042.65

(Exc. VAT)

GHS 1,251.18

(Inc. VAT)

Available For Order

* Delivery dates may change based on your quantity and address.

Shipping & Policy

Payment Methods:

Momo Page imagemastercardvise

Shipping Cost:

Contact the supplier about freight and estimated delivery time.

Secure payments:

Every payment you make on aptghana.com is protected by the platform.

Return policy

Enjoy peace of mind with our 7-day return policy for used items, provided they are returned in their original packaging.

Description

Specifications

Dimensions Drawings

3-Phase Supply and Motor Temperature Control Relays
Dimensions and Mounting



Connections and Schema

3-Phase Supply and Motor Temperature Control Relays
Wiring Diagram



Technical Description

Function Diagrams
Phase Sequence Control and Phase Failure Detection (U measured < 0.7 x nominal supply voltage)


Motor Temperature Control via PTC Probe


Legend

Un Nominal 3-phase supply voltage

R T1-T2 Resistance between terminals T1 and T2

11-14 R1 output relay connections

Relay status: black color = energized.

NOTE: The temperature control relay can take up to 6 PTC (positive temperature coefficient) probes wired in series between terminals T1 and T2.


,
Function Diagrams
Motor Temperature Control via PTC Probe

As soon as the temperature returns to the correct value, the relay can be unlocked (reset), either by pressing the "Test/Reset" button (for at least 200 ms), or by closing a volt-free contact (for at least 200 ms) between terminal Y1 and T1 (without a parallel load). When a fault is detected, the "temperature" output relay locks in the open position, even if the "Test/Reset" button is pressed.

With memory ("Memory" mode)


Use of the "Test/Reset" Button

When the temperature is normal, pressing the "Test/Reset" button simulates overheating, the "temperature" output relay contact is open.

Without memory ("No Memory" mode).


With memory ("Memory" mode)


Legend

Un Nominal 3-phase supply voltage

R T1-T2 Resistance between terminals T1 and T2

11-14 R1 output relay connections

Relay status: black color = energized.

In "Memory" mode, "fault" indication is locked and the button must be released then pressed again to reset the function. When a fault has been detected and the temperature has returned to normal, the "temperature" control relay can be unlocked (reset) by pressing the "Test/Reset" button.