Description

This product is part of the Modicon TM3 range, an offer of expansion I/O modules for Modicon M221, M241, M251 and M262. The discrete I/O module provides 16 input channels, 8 relay output channels with sink or source (positive/negative) discrete logic. It is an I/O module with a relay output voltage of 24V DC, 240V AC, a current consumption of 65mA, 5mA at 5V DC via bus connector. This product is capable of controlling variable speed drives or any device equipped with a current or voltage input. There is an Insulation between input/output and internal logic at 500V AC, input and output groups at 1500V AC, open contact at 750V AC and non-insulated between inputs/outputs. It is furnished with removable screw terminal for electrical connection with 3.81mm pitch adjustment for inputs and outputs. It is an IP20 rated product. Its dimensions are 42.9mm (Width) x 84.6mm (Depth) x 90mm (Height). It weighs 0.165kg. This product is certified by CE, CULus and C-Tick. It meets EN/IEC 61131-2 and EN/IEC 61010-2-201 standards. This module is compatible with Modicon M262, Modicon M241, Modicon M251 and Modicon M221 logic controller. It supports top hat type TH35-15, top hat type TH35-7.5 rail conforming to IEC 60715 and plate or panel with fixing kit mount. Modicon TM3 expansion modules have been designed with a simple interlocking assembly mechanism. A bus expansion connector is used to distribute data and the power supply when assembling the Modicon TM3 modules with logic controllers. Boost the performance of your controller with the Modicon TM3 I/O system specially designed for the Modicon M221, M241 and M251 logic controllers.

Specifications

Main
Range of product
Modicon TM3
Product or component type
Discrete I/O module
Range compatibility
Modicon M241
Modicon M251
Modicon M221
Modicon M262
Discrete input number
16 for input conforming to IEC 61131-2 Type 1
Discrete input logic
Sink or source (positive/negative)
Discrete input voltage
24 V
Discrete input current
7 mA for input
Discrete output type
Relay normally open
Discrete output number
8
Discrete output logic
Positive or negative
Discrete output voltage
24 V DC for relay output
240 V AC for relay output
Discrete output current
2000 mA for relay output
Complementary
Discrete I/O number
24
Current consumption
5 mA at 5 V DC via bus connector (at state off)
0 mA at 24 V DC via bus connector (at state on)
0 mA at 24 V DC via bus connector (at state off)
65 mA at 5 V DC via bus connector (at state on)
Discrete input voltage type
DC
Voltage state 1 guaranteed
15...28.8 V for input
Current state 1 guaranteed
>= 2.5 mA (input)
Voltage state 0 guaranteed
0...5 V for input

Dimensions Drawings

Dimensions


(*)
8.5 mm/0.33 in. when the clamp is pulled out.


Mounting and Clearance

Spacing Requirements



,
Mounting on a Rail


Incorrect Mounting



,
Mounting on a Panel Surface


(1)
Install a mounting strip

Mounting Hole Layout



Connections and Schema

Digital Mixed I/O Module (24-channel)
Wiring Diagram (Source)


(*)
Type T fuse
(1)
The COM0, COM1 and COM2 terminals are not connected internally.
(2)
To improve the life time of the contacts, and to protect from potential inductive load damage, it is recommended to connect a free wheeling diode in parallel to each inductive DC load or an RC snubber in parallel of each inductive AC load.
(A)
Sink wiring (positive logic)
(C)
Source wiring (positive logic)

Wiring Diagram (Sink)


(*)
Type T fuse
(1)
The COM0, COM1 and COM2 terminals are not connected internally.
(2)
To improve the life time of the contacts, and to protect from potential inductive load damage, it is recommended to connect a free wheeling diode in parallel to each inductive DC load or an RC snubber in parallel of each inductive AC load.
(B)
Source wiring (negative logic)
(D)
Sink wiring (negative logic)