Description

This product is part of the Modicon TM3 range, an offer of expansion I/O modules for Modicon M221, M241, M251 and M262. The analogue input module provides 8 inputs with 16bit and 15bit + sign resolution. It is an input module with a rated supply voltage of 24V DC and a current consumption of 30mA at 24V DC via external supply, 45mA/40mA at 5V DC via bus connector. This product is capable of controlling variable speed drives or any device equipped with a current or voltage input. There is an insulation between input and supply at 1500V AC, input and internal logic at 500V AC. It is furnished with removable screw terminal for electrical connection with pitch 3.81mm adjustment for inputs and supply. It is an IP20 rated product. Its dimensions are 23.6mm (Width) x 70mm (Depth) x 90mm (Height). It weighs 0.11kg. This product is certified by CE. It meets EN/IEC 61131-2 and EN/IEC 61010-2-201 standards. This module is compatible with Modicon M262, Modicon M241, Modicon M251 and Modicon M221 logic controller. It supports top hat type TH35-15, top hat type TH35-7.5 rail conforming to IEC 60715 and plate or panel with fixing kit mount. Modicon TM3 expansion modules have been designed with a simple interlocking assembly mechanism. A bus expansion connector is used to distribute data and the power supply when assembling the Modicon TM3 modules with logic controllers. Boost the performance of your controller with the Modicon TM3 I/O system specially designed for the Modicon M221, M241 and M251 logic controllers.

Specifications

Main
Range of product
Modicon TM3
Product or component type
Analog input module
Range compatibility
Modicon M221
Modicon M241
Modicon M251
Modicon M262
Analogue input number
8
Analogue input type
thermocouple - 200...1000 °C with thermocouple J
thermocouple - 200...1300 °C with thermocouple K
thermocouple 0...1760 °C with thermocouple R
thermocouple 0...1760 °C with thermocouple S
thermocouple 0...1820 °C with thermocouple B
thermocouple - 200...400 °C with thermocouple T
thermocouple - 200...1300 °C with thermocouple N
thermocouple - 200...800 °C with thermocouple E
thermocouple 0...2315 °C with thermocouple C
NTC 10k thermistor -90...150 °C
PTC thermistor 100...10000 Ohm
thermocouple - 200...1000 °C
Complementary
Analogue input resolution
16 bits
15 bits + sign
Input impedance
>= 1 MOhm thermocouple
>= 1 MOhm temperature probe
>= 1 MOhm thermistor
LSB value
0.1 °Cthermocouple
0.1 °C with NTC probe
1 Ohm with PTC/NTC probe
Conversion time
100 ms + 100 ms per channel + 1 controller cycle time
Sampling duration
100 ms
Absolute accuracy error
+/- 0.2 % of full scale at 25 °C for thermocouple C 0...2315 °C
+/- 6 °C at 25 °C for thermocouple R, S 0...200 °C
+/- 0.2 % of full scale at 25 °C for thermocouple R, S 200...1760 °C
+/- 0.2 % of full scale at 25 °C for thermocouple B 300...1820 °C
+/- 0.4 % of full scale at 25 °C for thermocouple K - 200...0 °C
+/- 0.2 % of full scale at 25 °C for thermocouple K 0...1300 °C
+/- 0.4 % of full scale at 25 °C for thermocouple J - 200...0 °C
+/- 0.2 % of full scale at 25 °C for thermocouple J 0...1000 °C
+/- 0.4 % of full scale at 25 °C for thermocouple E - 200...0 °C
+/- 0.2 % of full scale at 25 °C for thermocouple E 0...800 °C
+/- 0.4 % of full scale at 25 °C for thermocouple T - 200...0 °C
+/- 0.2 % of full scale at 25 °C for thermocouple T 0...400 °C
+/- 0.4 % of full scale at 25 °C for thermocouple N - 200...0 °C
+/- 0.2 % of full scale at 25 °C for thermocouple N 0...1300 °C

Dimensions Drawings

Dimensions


(*)
8.5 mm/0.33 in when the clamp is pulled out.


Mounting and Clearance

Spacing Requirements



,
Mounting on a Rail


Incorrect Mounting



,
Mounting on a Panel Surface


(1)
Install a mounting strip

Mounting Hole Layout



Connections and Schema

Analogue Input Module
Wiring Diagram (Thermocouple Input Type)


(*)
Type T fuse
(1)
Thermocouple

Wiring Diagram (Temperature Probe Input Type)


(*)
Type T fuse


help mobile view

Need more information?

Check with our technical team!

Contact Us