Description
This XPSAC safety module monitors emergency shutdown pushbuttons and limit switches. It meets the requirements of Performance Level PL e/Category 4 conforming to standard EN/ISO 13849-1 and SILCL3 conforming to EN/IEC 61508 and EN/IEC 62061. It can be used for monitoring emergency stop circuits conforming to standards EN/ISO 13850 and EN/IEC 60204-1. 24V AC/DC supply allows direct supply via an auxiliary transformer, like ABT7 or ABL6, allowing saving at installation time. It has additional solid-state output for communication with PLCs about safety status of your process.
Shipping & Policy
Payment Methods:

Shipping Cost:
Contact the supplier about freight and estimated delivery time.
Secure payments:
Every payment you make on aptghana.com is protected by the platform.
Return policy
Enjoy peace of mind with our 7-day return policy for used items, provided they are returned in their original packaging.
Specifications
Main | |
---|---|
Range of product | Preventa Safety automation |
Product or component type | Preventa safety module |
Safety module name | XPSAC |
Safety module application | For emergency stop and switch monitoring |
Function of module | Emergency stop Switch monitoring |
Safety level | Can reach PL e/category 4 conforming to EN/ISO 13849-1 Can reach SILCL 3 conforming to EN/IEC 62061 |
Safety reliability data | MTTFd = 210.4 years conforming to EN/ISO 13849-1 DC > 99 % conforming to EN/ISO 13849-1 PFHd = 3.56E-9 1/h conforming to EN/IEC 62061 |
Type of start | Unmonitored |
Connections - terminals | Captive screw clamp terminals, 1 x 0.14...1 x 2.5 mm² flexible without cable end Captive screw clamp terminals, 1 x 0.14...1 x 2.5 mm² solid without cable end Captive screw clamp terminals, 1 x 0.25...1 x 1.5 mm² flexible with cable end, with bezel Captive screw clamp terminals, 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel Captive screw clamp terminals, 2 x 0.14...2 x 0.75 mm² flexible without cable end Captive screw clamp terminals, 2 x 0.14...2 x 0.75 mm² solid without cable end Captive screw clamp terminals, 2 x 0.25...2 x 1 mm² flexible with cable end, without bezel Captive screw clamp terminals, 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel |
Output type | Relay instantaneous opening, 3 NO circuit(s), volt-free |
Number of additional circuits | 1 solid state output |
[Us] rated supply voltage | 24 V AC - 20...10 % 24 V DC - 20...20 % |
Complementary | |
---|---|
Supply frequency | 50/60 Hz |
Maximum power consumption in W | 1.2 W DC |
Maximum power consumption in VA | 2.5 VA AC |
[Uc] control circuit voltage | 24 V |
Breaking capacity | 180 VA holding AC-15 C300 relay output 1800 VA inrush AC-15 C300 relay output |
Breaking capacity | 1.5 A at 24 V (DC-13) time constant: 50 ms for relay output |