Description

This Vigi NG125 is a modular add-on residual current devices. It has 4P and rated current is 125A. The earth leakage protection class is A type with a sensitivity of 300mA and a voltage independent technology. This product protects against short circuit, cable overload, electrical shock by indirect contact and fire hazards. This device is combined with a NG125 circuit breaker to provide the earth leakage protection and circuit protection. This product is compliant with IEC 60947-2 standard. The Ue rated operational voltage is from 230VAC to 415VAC. The Ui rated insulation voltage is 690VAC. The Uimp rated impulse withstand voltage is 8kV. The pollution degree is 3. It can be mounted on 35 mm symmetrical DIN rail. The width in 9mm pitches is 11. The dimensions are (W) 207mm x (H) 118mm x (D) 81mm. The weight is 0.8kg. The degree of protection is IP20 and IP40 in an enclosure.

Compatible products

schneider-electric 19042 Picture

Circuit Breakers (1)

Specifications

Main
Range
Acti9
product name
Acti9 Vigi NG125
Product or component type
Add-on residual current device
Device short name
Vigi NG125
Poles description
4P
[In] rated current
125 A
Network type
AC
Earth-leakage sensitivity
300 mA
Earth-leakage protection time delay
Instantaneous
Earth-leakage protection class
Type A
Standards
IEC/EN 60947-2:Annex B
Complementary
Device location in system
Outgoer
Group incomer
Network frequency
50/60 Hz
[Ue] rated operational voltage
230...415 V AC 50/60 Hz
Residual current tripping technology
Voltage independent
[Ui] rated insulation voltage
690 V AC 50/60 Hz conforming to IEC/EN 60947-2
[Uimp] rated impulse withstand voltage
8 kV conforming to IEC/EN 60947-2