schneider-electric 56173 Picture
schneider-electric logo

residual current protection relay, Vigirex RH99M, 30 mA to 30 A, 220/240 VAC 50/60 Hz, DIN rail mounting

Mfr. Part No.:

56173

APT Stock No.:

SE-56173

Brand:

Schneider Electric

Mounting support:
DIN railFront panel
[Us] rated supply voltage:
12...24 V AC 50/60 Hz 55...120 %12...48 V DC 55...120 %110...130 V AC 50/60 Hz 55...110 %220...240 V AC 50/60 Hz 55...110 %380...415 V AC 50/60 Hz 55...110 %440...525 V AC 50/60 Hz 70...110 %

Back Order

Subtotal (1 unit)**

GHS 5,427.73

(Exc. VAT)

GHS 6,616.40

(Inc. VAT)

Available For Order

* Delivery dates may change based on your quantity and address.

Shipping & Policy

Payment Methods:

Momo Page imagemastercardvise

Shipping Cost:

Contact the supplier about freight and estimated delivery time.

Secure payments:

Every payment you make on aptghana.com is protected by the platform.

Return policy

Enjoy peace of mind with our 7-day return policy for used items, provided they are returned in their original packaging.

VigiPacT relays ensure coordination with ComPacT circuit breakers (switch off within 40ms)

Continuous monitoring of the power supply, the relay/toroid link and internal electronics

Reinforced insulation of VigiPacT relays (overvoltage category IV)

Access to settings protected by a lead-sealable cover or password

RoHS and REACH compliant

Description

VigiPacT RH99M is a DIN rail mounting residual current protection relay. It protects against people direct or indirect contact, property fire hazards and motors. It measures the earth leakage current in an electrical installation via its associated toroid. It trips the associated circuit breaker when the set residual operation current is overrun. The operational supply voltage is 220/240VAC 50/60Hz. The current sensitivity is selectable with 9 thresholds from 30 mA to 30 A. The time delay is selectable with 9 settings from instantaneous to 4.5s. It requires a local manual reset after a fault clearance. The monitored distribution system voltage is up to 1000 VAC 50/60/400 Hz. It is installed on a DIN-rail inside a switchboard and the protection degree is IP40. It must be associated with a compatible Schneider Electric type A toroid or rectangular sensor.

Compatible products

schneider-electric 56173 Picture

Sensors (7)

Specifications

Main
Range
VigiPacT
Device short name
RH99M
Product or component type
Residual current protection relay
Relay application
Protection relay
Mounting support
DIN rail
Earth-leakage protection class
Type A
Type of setting
Selector
Residual earth-leakage sensitity adjustment type
Adjustable 9 settings
Earth-leakage sensitivity
0.03…30 A
Earth-leakage time delay
Instantaneous for 0.03 A
Adjustable 9 settings 0…4.5 s for 0.03…30 A
Current sensors compatibility
VigiPacT TOA earth leakage current sensor
VigiPacT A earth leakage current sensor
VigiPacT L earth leakage current sensor
[Ithe] conventional enclosed thermal current
8 A
Minimum load
10 mA at 12 V
[Us] rated supply voltage
220...240 V AC 50/60 Hz 55...110 %
Power consumption in VA
4 VA
Monitored distribution system
1000 V - AC at 50/60 Hz (maximum)
1000 V - AC at 400 Hz (maximum)
Earthing system
TN-S
TT
IT
[Uimp] rated impulse withstand voltage
8 kV
Reset
Manual reset
Complementary
Test function
Remote test
Local
Monitoring
Electronics (continuous)
Power supply (continuous)
Relay/sensor link (continuous)
Type of measurement
Earth fault current internal measurement, range: 80...100 %
Tamperproof of settings
Protected by sealable cover
Connections - terminals
Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12
Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² rigid AWG 24...AWG 12
Auxiliary power supply: terminal block cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12
Fault: screw terminal cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12
Fault: screw terminal cable(s) 0.2…4 mm² rigid AWG 24...AWG 12
Fault: screw terminal cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12
Relay test and fault reset: screw terminal cable(s) 0.14…1 mm² flexible AWG 26...AWG 16
Relay test and fault reset: screw terminal cable(s) 0.14…1.5 mm² rigid AWG 26...AWG 16
Relay test and fault reset: screw terminal cable(s) 0.25…0.5 mm² flexible AWG 26...AWG 16
Sensor: screw terminal cable(s) 0.14…1 mm² flexible AWG 26...AWG 16
Sensor: screw terminal cable(s) 0.14…1.5 mm² rigid AWG 26...AWG 16
Sensor: screw terminal cable(s) 0.25…0.5 mm² flexible AWG 26...AWG 16
Voltage presence: screw terminal cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12
Voltage presence: screw terminal cable(s) 0.2…4 mm² rigid AWG 24...AWG 12
Voltage presence: screw terminal cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12
Wire stripping length
Auxiliary power supply: 7 mm for top connection
Fault: 8 mm for bottom connection
Relay test and fault reset: 5 mm for bottom connection
Sensor: 5 mm for top connection
Voltage presence: 8 mm for bottom connection
help mobile view

Need more information?

Check with our technical team!

Contact Us