schneider-electric la1kn04 Picture
schneider-electric logo

TeSys K - Auxiliary contact block - 4 NC - screw-clamps terminals

Mfr. Part No.:

LA1KN04

APT Stock No.:

SE-LA1KN04

Brand:

Schneider Electric

Back Order

Subtotal (1 unit)**

GHS 159.97

(Exc. VAT)

GHS 195.00

(Inc. VAT)

Available For Order

* Delivery dates may change based on your quantity and address.

Shipping & Policy

Payment Methods:

Momo Page imagemastercardvise

Shipping Cost:

Contact the supplier about freight and estimated delivery time.

Secure payments:

Every payment you make on aptghana.com is protected by the platform.

Return policy

Enjoy peace of mind with our 7-day return policy for used items, provided they are returned in their original packaging.

Meet the need for more control contact for TeSys K contactor and control relay

Easy choice for simple applications

Description

TeSys K instantaneous auxiliary contact block, for contactors LC.K, LP.K, CA.K with screw clamp terminals (except LP4K, LP5K, CA4K). It provides 4NC contacts rated up to 10A 690V AC, connection by screw clamp terminals. Front mounting by clip-on, it procures high reliability and durability. Multi standards certified (IEC, UL, CSA, CCC),

Compatible products

schneider-electric la1kn04 Picture

MAINFUNCTIONS (4)

Specifications

Main
Range
TeSys
product name
TeSys K
Product or component type
Auxiliary contact block
Device short name
LA1
Range compatibility
TeSys K LC1K
TeSys K CA2K
TeSys K CA3K
Mounting location
Front
Pole contact composition
4 NC
Contacts operation
Instantaneous
[Ue] rated operational voltage
690 V AC 25...400 Hz
[Ui] rated insulation voltage
690 V conforming to IEC 60947-5-1
600 V conforming to UL 60947-5-1
600 V conforming to CSA C22.2 No 60947-5-1
[Ith] conventional free air thermal current
10 A (at 50 °C)
Standards
EN/IEC 60947-5-1
UL 60947-5-1
CSA C22.2 No 60947-5-1
GB/T 14048.5
JIS C8201-5-1
UL 60335-2-40:Annex JJ
Product certifications
CB Scheme
CCC
UL
CSA
CE
UKCA
Complementary
Irms rated making capacity
110 A at <= 690 V AC conforming to IEC 60947
Permissible short-time rating
80 A 1 s
60 A 500 ms
110 A 100 ms
Associated fuse rating
10 A gG at <= 690 V conforming to IEC 60947
Minimum switching current
5 mA
Minimum switching voltage
17 V
Non overlap distance
0.5 mm
help mobile view